Centralized space for telecommunications equipment
- Shall house only equipment directly related to the telecommunications system and its environmental support systems
- Sizing:
- To meet known requirements of specific equipment
- If equipment is unknown, plan for 0.07 m2 (0.75 ft2) of equipment room space for every 10 m2 (100 ft2) of work station space
- Must be a minimum of 14 m2 (150 ft2)
- For special-use buildings, size must be based on number of work stations as follows:
Equipment Room Floor Space for Special-use Buildings
Area Work Stations (m2) (ft2) Up to 100 14 150 101 to 400 37 400
401 to 800 74 800 801 to 1200 111 1200
|