- Consists of the telecommunications service entrance to the building, including the entrance point through the wall, and continuing to the entrance room or space
- May contain the backbone pathways that link to other buildings in campus environments
- Sizing:
Minimum Equipment and Termination Wall Space
Gross Floor Space Wall Length (m2) (ft2) (mm) (in) 500 5000 990 39 1000 10000 990 39
2000 20000 1060 42 4000 40000 1725 68 5000 50000 2295 90 6000 60000 2400 96
8000 80000 3015 120 10000 100000 3630 144
Minimum Equipment and Termination
Room Space Gross Floor Space Room Dimensions (m2) (ft2) (mm) (in)
7000 70000 3660 x 1930 12 x 6.3 10000 100000 3660 x 1930 12 x 6.3 20000 200000 3660 x 2750 12 x 9
40000 400000 3660 x 3970 12 x 13 50000 500000 3660 x 4775 12 x 15.6 60000 600000 3660 x 5588 12 x 18.3
80000 800000 3660 x 6810 12 x 22.3 100000 1000000 3660 x 8440 12 x 27.7
SEPARATION FROM ELECTROMAGNETIC ENERGY SOURCES
- As of this printing, separation of telecommunication circuits from power circuits is being studied by the TIA/EIA.
|