| Item | ADP8235 6kVA | ADP8245 12kVA |
| General |
| Power | 6kVA/4kW | 12kVA/8kW |
| Nominal input voltage | 84/120/160 to
265V without using battery power |
| Frequency
range | 50/60Hz |
| Power
factor (Total Harmonics Distortion Input side) | 0.99 (<5%) |
| Sinusoidal output
voltage | 104/120/208/240V |
| Efficiency | 93% | 93% |
| Crest
factor | 3.1 | 3.1 |
| Short circuit current
(A) | 82 | 164 |
| Overload capacity
(inverter) | 160% |
| Batteries |
| Standard backup
time | Full load | 9 min (1 battery module) | 9 min (2
battery modules) |
| Half load | 23 min (1 battery
module) | 23 min (2 battery modules) |
| Automatic
battery test | Every day/Once a week/Once a
month |
| Typical recharge time | 2H45 |
| Battery Type | 5Ah |
| Remote Emergency Power Off | Yes |
| Communications |
| Port | 1 RS232/U-Talk + 2 communications slots |
| Management software included | Solution-Pac & UPS driver |
| Optional
cards for UPS or Multislot module | SNMP ; 2 RS232
U-Talk or Basic (volt-free contacts) ports ; RS232 or RS485 Jbus/ModBus ;
6 relay contacts 250V 2A ; USB ; 2 RS232 COM ports (HID protocol) ; 2
AS400 (volt-free contacts) or/and remote shutdown ports |
| Environmental |
| Acoustic
noise | 45 dB |
| Operating
temperature | 0 to 40C |
| Altitude | 3280 feet |
| Conformance |
| Approvals | UL, cUL, ISO 9001, ISO 14001 |
| Warranty | 2 years, repair or
replace |