Dedicated to telecommunications function and support facilities only Minimum of one closet per floor
Additional closets should be provided for each area up to 1000 m2 (10,000 ft2) when:
The floor area served exceeds 1000 m2 (10000 ft2)
The horizontal distance exceeds 90 m (300 ft)
Recommended Closet Sizing
(based on 1 work station per 10m2 [100ft2])
Serving Area Closet Size
(m2) (ft2) (m2) (ft2)
1000 10000 3000 x 3400 10 x 11
800 8000 3000 x 2800 10 x 9
500 5000 3000 x 2200 10 x 7